FLOYD F60 — Wood Chip Quality Reference Guide
Biomass Fuel Specification · EN ISO 17225-4 · GLOCK Standard
The FLOYD F60 CHP system requires high-quality wood chips to operate reliably and efficiently. The gasifier is sensitive to fuel quality — sub-standard chips cause gasifier blockages, tar formation, reduced gas quality, and unplanned downtime.
This reference guide defines acceptable fuel parameters per EN ISO 17225-4 and provides real photo examples to help operators and suppliers identify compliant material at delivery.
Key consumption: 55 kg/h of dry biomass at full load (60 kW electric · 130 kW thermal).
Clean hardwood chips
Uniform chip size, clean flat cuts, no shredding or excessive fines. Moisture content within specification.
- Length: 20–40 mm predominantly
- Main fraction: >60% in 16-45mm range
- Colour: light-medium brown (dry)
- No visible dust layer
Mixed hardwood/softwood chips
Chipped from clean construction offcuts. Suitable piece size with minimal fines fraction.
- Length: 16–45 mm range (main fraction)
- Maximum length: <70 mm
- No painted or treated material
- Low ash content (clean wood only)
Forestry residue chips
High-quality forestry chips. Slightly coarser but within tolerance. Well-dried and consistent.
- Length: 30–50 mm (within main fraction)
- Some coarse fraction 45-65mm (≤8% allowed)
- Fines: minimal (<2% small fraction)
- Good feed characteristics
Excessive fines content
High proportion of dust and particles under 8 mm. Causes bridging and poor gas flow through the gasifier bed.
- Fines: visibly >5% small fraction (<8mm)
- Dusty appearance on delivery
- Risks: feed blockages, dust explosions
- Will need screening — or reject
Shredded wood (fibrous)
Material produced by shredders or grinders instead of chippers. Fibrous texture compacts in feed system and blocks screws.
- Form: shredded/ground, not chipped
- Texture: fibrous, compactable
- Risks: major feed system blockages
- Reject on delivery — do not use
Oversized chips (length)
Chips exceed 70 mm maximum length specification. Will jam screw conveyor and disrupt gasifier loading.
- Length: many pieces >70–100 mm
- Exceeds maximum length limit
- Risks: conveyor jams, uneven gasification
- Require screening before use
| Parameter | Target Value (F60) | Tolerance / Action Thresholds | Delivery Action | Explanation |
|---|---|---|---|---|
| Moisture Content | 5% ≤ m ≤ 13% | >13%: dryer needed · >15%: reject | ✓ OK 5-13% | Higher moisture reduces gasification efficiency and gas quality. |
| Chip Length (Main Fraction) | 16–45 mm (≥60% mass) | 45–65mm coarse: ≤8% · >70mm: reject | ⚠ Screen if mixed | Main fraction must be 16-45mm. Coarse fraction 45-65mm allowed up to 8%. |
| Maximum Length (L) | ≤ 70 mm | >70mm: screen or reject | ⚠ Screen oversized | Oversized chips block screw conveyor (see bad-3 photo above). |
| Coarse Fraction (45-65mm) | ≤ 8% | >8%: may need screening | ⚠ Check distribution | Coarse fraction 45-65mm allowed up to 8% of mass per GLOCK standard. |
| Fines — large (8-16mm) | ≤ 20% | >20%: borderline, may need screening | ⚠ Monitor closely | Large fines (8mm ≤ max. 20% < 16mm) affect feed consistency. |
| Fines — small (<8mm) | ≤ 2% | 2–5%: borderline · >5%: reject | ✗ Reject >5% | Small fines (<8mm) cause bridging and reduced gas flow (see bad-1 photo). |
| Chip Form | Chipped only | Shredded material: reject | ✗ Reject shredded | Shredded wood compacts and blocks feed system (see bad-2 photo). |
| Wood Type | Clean wood only | Painted/treated/MDF: reject | ✓ Clean wood OK | Contaminated wood releases harmful gases during gasification. |
| Ash Content | < 1% | >1%: monitor closely | ✓ Typically OK | Pure wood chips are naturally low in ash. Quality A1-B2 per EN ISO 17225-4. |
Compliant Chips
No additional investment. System runs at full efficiency with 55 kg/h consumption at rated load.
Screening Unit Required
One-time investment. Handles oversized chips and excessive fines. Recommended for inconsistent supply.
Biomass Dryer Required
For moisture 13–15%. Uses 40 kW CHP heat, 3 kW electric, 3t/day output. Max 2 CHP units per dryer.
Unplanned Downtime
Gasifier cleaning per blockage incident. Reject non-compliant deliveries to avoid this cost.
Required Additional Equipment
Select any additional equipment needed based on your fiber quality. Costs will be automatically added to the configurator.
✓ Accept Delivery If:
- ✓Chips are clean-cut and flat — not fibrous or shredded
- ✓Colour is light to medium brown (dry)
- ✓Length predominantly 16–45 mm (main fraction ≥60%)
- ✓Maximum length ≤ 70 mm
- ✓No visible dust clouds on delivery
- ✓Moisture meter reads 5-13%
- ✓No painted, treated, or MDF wood present
- ✓EN ISO 17225-4 supplier certificate available
✗ Reject or Escalate If:
- ✗Material is shredded / has fibrous texture (like bad-2)
- ✗Chips obviously > 70 mm in length (like bad-3)
- ✗Heavy dust / fines visible in load (like bad-1)
- ✗Dark green-brown colour (high moisture)
- ✗Moisture meter reads <5% or >15%
- ✗Painted, lacquered, or MDF material visible
- ✗Soil, stones, or other contamination present
- ✗No quality documentation from supplier
Fiber Consumption & Load Factor
The F60 consumes 55 kg/h of dry biomass at 100% load (60 kW electric · 130 kW thermal). At minimum load (75%), consumption drops to ~41 kg/h. Poor chip quality reduces gasifier stability and can cause load fluctuations even at correct feed rate.
Dryer Unit Integration (Moisture 13–15%)
The optional dryer uses 40 kW of waste heat from the CHP (no reduction to electrical output) plus 3 kW electric. It processes up to 3 tonnes/day and reduces moisture to 5-10% (within specification range). A maximum of 2 F60 units can share one dryer. Investment: approximately $100,000.
Storage Recommendations
Store chips under cover to prevent moisture re-absorption. Use first-in/first-out stock rotation. Keep pile height under 3 m with adequate air circulation to prevent self-heating. Avoid direct sun exposure on the pile surface.
Standard Reference
All specifications follow EN ISO 17225-4 (Solid biofuels — Fuel specifications and classes — Part 4: Graded wood chips) and the GLOCK internal quality standard. For certification questions, contact your FLOYD technical representative.